MS20-0800SAAEHH01.0. |
|
|
Reference product |
|
Product
description |
Description |
ETHERNET/Fast ETHERNET-switch
according to IEEE 802.3 modular, managed, Industrial switch
for DIN rail store-and-forward-switching, fanless design,
Software Layer 2 Enhanced |
|
Port type and quantity |
Fast ethernet ports in
total: 8; Gigabit ethernet ports: 0 |
|
Type |
MS20-0800SAAEHH01.0. |
|
Order No. |
MS20-0800SAAEHH01.0. |
|
More
Interfaces |
Power supply/signaling
contact |
2 x plug-in terminal block,
6-pin |
|
V.24 interface |
1 x RJ11 socket |
|
USB interface |
1 x to connect auto-configuration
adapter ACA21-USB |
|
Network
size - cascadibility |
Line - / star topology |
Any |
|
Ring structure (HIPER-Ring) |
50 (reconfiguration time
< 0.3 sec.) |
|
Power
requirements |
Operating voltage |
24 V DC (18-32) V |
|
Current consumption at
24 V DC |
208.0 mA |
|
Current consumption at
48 V DC |
155.0 mA |
|
Power output in Btu (IT)
h |
17.07750 |
|
Software |
Management |
Serial interface, web-interface,
SNMP V1/V2, HiVision file transfer SW HTTP/TFTP |
|
Diagnostics |
LEDs (power, link status,
data, 100 Mbit/s, autonegotiation, full-duplex, error,
redundancy management, ring-port, LED test), log-file,
syslog, signal contact, RMON (statistics, history, alarme,
events), port mirroring, topology discovery 802.1AB |
|
Configuration |
Comand line interface
(CLI), TELNET, BootP, DHCP, DHCP option 82, HIDiscovery,
auto-configuration adapter (ACA21-USB) |
|
Security |
Port security (IP and
MAC), SNMP V3 (no encryption) |
|
Redundancy functions |
HIPER-ring (ring structure),
RSTP 802.1w, redundant network/ring coupling, dual homing,
redundant 24 V power supply, redundant signal contact
(only MICE) |
|
Filter |
QoS 4 classes, priorisation
(IEEE 802.1D/p), VLAN (IEEE 802.1Q), multicast (IGMP snooping/querier),
multicast detection unknown multicast, broadcastlimiter,
fast aging |
|
Realtime |
SNTP server, PTP / IEEE
1588 support with media module (only MICE) |
|
Flow control |
Flow control 802.3x, port
priority 802.1D/p, priority (TOS/DIFFSERV) |
|
Ambient
conditions |
Operating temperature |
0º to +60ºC |
|
Storage/transport temperature |
-40º to +70ºC |
|
Relative humidity (non-condensing) |
10% to 95% |
|
MTBF |
54.65 years |
|
Mechanical
construction |
Dimensions (W x H x D) |
125 x 133 x 100 (140 at
48 V module) |
|
Mounting |
DIN Rail |
|
Weight |
610 g (700 g at 48 V module) |
|
Protection class |
IP20 |
|
Mechanical
stability |
IEC 60068-2-27 shock |
15 g, 11 ms duration,
18 shocks |
|
IEC 60068-2-6 vibration |
1 mm, 2 Hz - 13.2 Hz,
90 min.; 0.7g, 13,2 Hz - 100 Hz, 90 min.; 3.5 mm, 3 Hz
- 9 Hz, 10 cycles, 1 octave/min.; 1g, 9 Hz - 150 Hz, 10
cycles, 1 octave/min. |
|
EMC
interference immunity |
EN 61000-4-2 electrostatic
discharge (ESD) |
6 kV contact discharge,
8 kV air discharge |
|
EN 61000-4-3 electromagnetic
field |
6 kV contact discharge,
8 kV air discharge |
|
EN 61000-4-4 fast transients
(burst) |
2 kV power line, 1 kV
data line |
|
EN 61000-4-5 surge voltage |
power line: 2 kV (line/earth),
1 kV (line/line), 1 kV data line |
|
EN 61000-4-6 conducted
immunity |
3 V (10 kHz - 150 kHz),
10 V (150 kHz - 80 MHz) |
|
EMC
emitted immunity |
FCC CFR47 Part 15 |
FCC CFR47 part 15 class
A |
|
EN 55022 |
EN 55022 class A |
|
Approvals |
Safety of industrial control
equipment |
cUL 508 (pending) |
|
Hazardous locations |
cUL 1604 class1 div 2
(pending) |
|
Scope
of delivery and accessories |
Scope of delivery |
Device, terminal block,
operating manual |
|
Accessories to order separately |
Rail power supply RPS
30, RPS 60 or RPS 120, terminal cable, network management
HiVision, auto-configuration adapter (ACA21-USB), 19"
installation frame |
|