OZD Modbus Plus G12 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Product description |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Description |
 |
 |
 |
interface converter electrical/optical for Modbus Plus-field bus networks; repeater
function; for quartz glass und PCF (HCS) FO; approval for Ex-zone 2 (Class 1, Div. 2) |
 |
 |
 |
 |
 |
 |
 |
Port type and quantity |
 |
 |
 |
2 x optical: 4 sockets BFOC 2.5 (STR)
1 x electrical: Sub-D 9-pin, female, pin assignment according to Modbus Plus-Standard |
 |
 |
 |
 |
 |
 |
 |
Type |
 |
 |
 |
OZD Modbus Plus G12 |
 |
 |
 |
 |
 |
 |
 |
Order No. |
 |
 |
 |
943 740-021 |
 |
 |
 |
 |
 |
 |
 |
Electrical interface |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Signal type |
 |
 |
 |
Modbus Plus |
 |
 |
 |
 |
 |
 |
 |
Bit rate |
 |
 |
 |
1 Mbit/s |
 |
 |
 |
 |
 |
 |
 |
Signal delay time (optional input/output) |
 |
 |
 |
<1 µs |
 |
 |
 |
 |
 |
 |
 |
Input/output signal |
 |
 |
 |
Modbus Plus Bus |
 |
 |
 |
 |
 |
 |
 |
Length of Modbus cable |
 |
 |
 |
100 m |
 |
 |
 |
 |
 |
 |
 |
Connection capability |
 |
 |
 |
max. 31 terminal devices |
 |
 |
 |
 |
 |
 |
 |
Terminator |
 |
 |
 |
external |
 |
 |
 |
 |
 |
 |
 |
Galvanic isolation |
 |
 |
 |
shielding/housing: no; data lines/housing: yes |
 |
 |
 |
 |
 |
 |
 |
Optical interface |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Wavelength |
 |
 |
 |
860 nm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in multi-mode fiber (MM) 50/125 |
 |
 |
 |
-15 dBm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in multi-mode fiber (MM) 62.5/125 |
 |
 |
 |
-14 dBm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in multi-mode fiber (MM) HCS 200/230 |
 |
 |
 |
-10 dBm |
 |
 |
 |
 |
 |
 |
 |
Optical input power |
 |
 |
 |
min. -25 dBm, max. -3 dBm |
 |
 |
 |
 |
 |
 |
 |
Cascadibility |
 |
 |
 |
not limited |
 |
 |
 |
 |
 |
 |
 |
More Interfaces |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Power supply |
 |
 |
 |
5-pin terminal block, screw mounting |
 |
 |
 |
 |
 |
 |
 |
Signaling contact |
 |
 |
 |
5-pin terminal block, screw mounting |
 |
 |
 |
 |
 |
 |
 |
Network size - length of cable |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Multimode fiber (MM) 50/125 µm |
 |
 |
 |
2300 m
10 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve |
 |
 |
 |
 |
 |
 |
 |
Multimode fiber (MM) 62.5/125 µm |
 |
 |
 |
2300 m
11 dB link budget at 860 nm; A = 3.5 dB/km, 3 dB reserve |
 |
 |
 |
 |
 |
 |
 |
Multimode fiber HCS (MM) 200/230 µm |
 |
 |
 |
1500 m
16 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve |
 |
 |
 |
 |
 |
 |
 |
Power requirements |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Operating voltage |
 |
 |
 |
24 VDC -20% ... 48 VDC +10% non-interchangeable, safety extra-low voltage |
 |
 |
 |
 |
 |
 |
 |
Current consumption |
 |
 |
 |
120 mA at +24 VDC; 65 mA at + 48 VDC |
 |
 |
 |
 |
 |
 |
 |
Power consumption |
 |
 |
 |
3.1 W |
 |
 |
 |
 |
 |
 |
 |
Redundancy |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Redundancy functions |
 |
 |
 |
HIPER-Ring (ring structure), redundant 24 V infeed |
 |
 |
 |
 |
 |
 |
 |
Displays |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
LED red/green (system) |
 |
 |
 |
monitoring operating voltage and data traffic |
 |
 |
 |
 |
 |
 |
 |
LED green/orange (Port 1) |
 |
 |
 |
differentiated monitoring electrical channel |
 |
 |
 |
 |
 |
 |
 |
LED green/orange (Port 2,3) |
 |
 |
 |
differentiated monitoring optical channels |
 |
 |
 |
 |
 |
 |
 |
Ambient conditions |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Operating temperature |
 |
 |
 |
0 °C to +60 °C |
 |
 |
 |
 |
 |
 |
 |
Storage/transport temperature |
 |
 |
 |
-40 °C to +70 °C |
 |
 |
 |
 |
 |
 |
 |
Relative humidity |
 |
 |
 |
<95% (non-condensing) |
 |
 |
 |
 |
 |
 |
 |
Mechanical construction |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Dimensions (W x H x D) |
 |
 |
 |
40 x 111 x 73.5 mm |
 |
 |
 |
 |
 |
 |
 |
Mounting |
 |
 |
 |
DIN rail or mounting plate |
 |
 |
 |
 |
 |
 |
 |
Weight |
 |
 |
 |
620 g |
 |
 |
 |
 |
 |
 |
 |
Protection class |
 |
 |
 |
IP 40 |
 |
 |
 |
 |
 |
 |
 |
Housing material |
 |
 |
 |
die-cast zink |
 |
 |
 |
 |
 |
 |
 |
EMC interference immunity |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-2 electrostatic discharge (ESD) |
 |
 |
 |
contact discharge: 4 kV, air discharge: 8 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-3 electromagnetic field |
 |
 |
 |
10 V/m (80 - 1000 MHz) |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-4 fast transients (burst) |
 |
 |
 |
power line 2 kV, data line: 1 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-5 surge voltage |
 |
 |
 |
power line 0.5 kV (line/line, line/earth), data line: 1 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-6 conducted immunity |
 |
 |
 |
10 V (0.15 - 80 MHz) |
 |
 |
 |
 |
 |
 |
 |
EMC emitted immunity |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
EN 55022 |
 |
 |
 |
EN 55022 limit class A |
 |
 |
 |
 |
 |
 |
 |
Approvals |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Issued approvals |
 |
 |
 |
cUL Class 1, Div.2; C-Tick |
 |
 |
 |
 |
 |
 |
 |
Scope of delivery and accessories |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Scope of delivery |
 |
 |
 |
device, start-up instructions |
 |
 |
 |
 |
 |
 |
 |
Accessories to order separately |
 |
 |
 |
manual, order no. 933 989-901 |
 |
 |
 |
 |