OZD Modbus Plus G12 |
|
|
|
|
|
|
|
|
|
|
Product description |
|
|
|
|
|
|
|
|
|
|
|
Description |
|
|
|
interface converter electrical/optical for Modbus Plus-field bus networks; repeater
function; for quartz glass und PCF (HCS) FO; approval for Ex-zone 2 (Class 1, Div. 2) |
|
|
|
|
|
|
|
Port type and quantity |
|
|
|
2 x optical: 4 sockets BFOC 2.5 (STR)
1 x electrical: Sub-D 9-pin, female, pin assignment according to Modbus Plus-Standard |
|
|
|
|
|
|
|
Type |
|
|
|
OZD Modbus Plus G12 |
|
|
|
|
|
|
|
Order No. |
|
|
|
943 740-021 |
|
|
|
|
|
|
|
Electrical interface |
|
|
|
|
|
|
|
|
|
|
|
Signal type |
|
|
|
Modbus Plus |
|
|
|
|
|
|
|
Bit rate |
|
|
|
1 Mbit/s |
|
|
|
|
|
|
|
Signal delay time (optional input/output) |
|
|
|
<1 µs |
|
|
|
|
|
|
|
Input/output signal |
|
|
|
Modbus Plus Bus |
|
|
|
|
|
|
|
Length of Modbus cable |
|
|
|
100 m |
|
|
|
|
|
|
|
Connection capability |
|
|
|
max. 31 terminal devices |
|
|
|
|
|
|
|
Terminator |
|
|
|
external |
|
|
|
|
|
|
|
Galvanic isolation |
|
|
|
shielding/housing: no; data lines/housing: yes |
|
|
|
|
|
|
|
Optical interface |
|
|
|
|
|
|
|
|
|
|
|
Wavelength |
|
|
|
860 nm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) 50/125 |
|
|
|
-15 dBm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) 62.5/125 |
|
|
|
-14 dBm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) HCS 200/230 |
|
|
|
-10 dBm |
|
|
|
|
|
|
|
Optical input power |
|
|
|
min. -25 dBm, max. -3 dBm |
|
|
|
|
|
|
|
Cascadibility |
|
|
|
not limited |
|
|
|
|
|
|
|
More Interfaces |
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
5-pin terminal block, screw mounting |
|
|
|
|
|
|
|
Signaling contact |
|
|
|
5-pin terminal block, screw mounting |
|
|
|
|
|
|
|
Network size - length of cable |
|
|
|
|
|
|
|
|
|
|
|
Multimode fiber (MM) 50/125 µm |
|
|
|
2300 m
10 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
Multimode fiber (MM) 62.5/125 µm |
|
|
|
2300 m
11 dB link budget at 860 nm; A = 3.5 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
Multimode fiber HCS (MM) 200/230 µm |
|
|
|
1500 m
16 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
Power requirements |
|
|
|
|
|
|
|
|
|
|
|
Operating voltage |
|
|
|
24 VDC -20% ... 48 VDC +10% non-interchangeable, safety extra-low voltage |
|
|
|
|
|
|
|
Current consumption |
|
|
|
120 mA at +24 VDC; 65 mA at + 48 VDC |
|
|
|
|
|
|
|
Power consumption |
|
|
|
3.1 W |
|
|
|
|
|
|
|
Redundancy |
|
|
|
|
|
|
|
|
|
|
|
Redundancy functions |
|
|
|
HIPER-Ring (ring structure), redundant 24 V infeed |
|
|
|
|
|
|
|
Displays |
|
|
|
|
|
|
|
|
|
|
|
LED red/green (system) |
|
|
|
monitoring operating voltage and data traffic |
|
|
|
|
|
|
|
LED green/orange (Port 1) |
|
|
|
differentiated monitoring electrical channel |
|
|
|
|
|
|
|
LED green/orange (Port 2,3) |
|
|
|
differentiated monitoring optical channels |
|
|
|
|
|
|
|
Ambient conditions |
|
|
|
|
|
|
|
|
|
|
|
Operating temperature |
|
|
|
0 °C to +60 °C |
|
|
|
|
|
|
|
Storage/transport temperature |
|
|
|
-40 °C to +70 °C |
|
|
|
|
|
|
|
Relative humidity |
|
|
|
<95% (non-condensing) |
|
|
|
|
|
|
|
Mechanical construction |
|
|
|
|
|
|
|
|
|
|
|
Dimensions (W x H x D) |
|
|
|
40 x 111 x 73.5 mm |
|
|
|
|
|
|
|
Mounting |
|
|
|
DIN rail or mounting plate |
|
|
|
|
|
|
|
Weight |
|
|
|
620 g |
|
|
|
|
|
|
|
Protection class |
|
|
|
IP 40 |
|
|
|
|
|
|
|
Housing material |
|
|
|
die-cast zink |
|
|
|
|
|
|
|
EMC interference immunity |
|
|
|
|
|
|
|
|
|
|
|
EN 61000-4-2 electrostatic discharge (ESD) |
|
|
|
contact discharge: 4 kV, air discharge: 8 kV |
|
|
|
|
|
|
|
EN 61000-4-3 electromagnetic field |
|
|
|
10 V/m (80 - 1000 MHz) |
|
|
|
|
|
|
|
EN 61000-4-4 fast transients (burst) |
|
|
|
power line 2 kV, data line: 1 kV |
|
|
|
|
|
|
|
EN 61000-4-5 surge voltage |
|
|
|
power line 0.5 kV (line/line, line/earth), data line: 1 kV |
|
|
|
|
|
|
|
EN 61000-4-6 conducted immunity |
|
|
|
10 V (0.15 - 80 MHz) |
|
|
|
|
|
|
|
EMC emitted immunity |
|
|
|
|
|
|
|
|
|
|
|
EN 55022 |
|
|
|
EN 55022 limit class A |
|
|
|
|
|
|
|
Approvals |
|
|
|
|
|
|
|
|
|
|
|
Issued approvals |
|
|
|
cUL Class 1, Div.2; C-Tick |
|
|
|
|
|
|
|
Scope of delivery and accessories |
|
|
|
|
|
|
|
|
|
|
|
Scope of delivery |
|
|
|
device, start-up instructions |
|
|
|
|
|
|
|
Accessories to order separately |
|
|
|
manual, order no. 933 989-901 |
|
|
|
|