Industrial Networking
FiberINTERFACES
Digital
Field Bus
Universal RS 485 Fiberoptic Repeaters
PROFIBUS Fiberoptic Repeaters
Genius Bus Fiberoptic Repeaters
FIP Bus Fiberoptic Repeaters
Modbus Plus Fiberoptic Repeaters
Video
Hybrids modules and OptoQuick components
Accessories
Industrial Ethernet
Hirschmann Networks
         
OZD Profi 12M G11
Product description
Description interface converter electrical/optical for PROFIBUS-field bus networks;
repeater function; for quartz glass FO; approval for Ex-zone 2 (Class 1, Div. 2)
Port type and quantity 1 x optical: 2 sockets BFOC 2.5 (STR)
1 x electrical: Sub-D 9-pin, female, pin assignment according to EN 50170 part 1
Type OZD Profi 12M G11
Order No. 943 727-221
Electrical interface
Signal type PROFIBUS (DP-V0, DP-V1, DP-V2 und FMS)
Bit rate 9.6; 19.2; 45.45; 93.75; 187.5; 500 kbit/s;
1.5; 3; 6; 12 Mbit/s (automatic setting)
Signal delay time (optional input/output) <= 6.5 bit times
Input/output signal RS 485 level
Input voltage range -7 V ... +12 V
Galvanic isolation no
Optical interface
Wavelength 860 nm
Launchable optical power in multi-mode fiber (MM) 50/125 -15 dBm
Launchable optical power in multi-mode fiber (MM) 62.5/125 -13 dBm
Launchable optical power in multi-mode fiber (MM) HCS 200/230 -10 dBm (transmitting power default)
Optical input power min. -28 dBm, max. -3 dBm
Cascadibility not limited
More Interfaces
Power supply 5-pin terminal block, screw mounting
Signaling contact 5-pin terminal block, screw mounting
Measuring outputs "Optical input power" 2 mm sockets
Network size - length of cable
Multimode fiber (MM) 50/125 µm 3000 m
13 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve
Multimode fiber (MM) 62.5/125 µm 3000 m
15 dB link budget at 860 nm; A = 3.5 dB/km, 3 dB reserve
Multimode fiber HCS (MM) 200/230 µm 1000 m
18 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve
Power requirements
Operating voltage 18 ... 32 VDC, typ. 24 VDC
Galvanic isolation yes
Current consumption max. 200 mA
Power consumption 4.8 W
Output voltage/output current (pin6) 5 VDC +5%, -10%, short circuit-proof/90 mA
Redundancy
Redundancy functions redundant 24 V infeed
Displays
LED red/green (system) monitoring operating voltage and bit rate
LED red/yellow (CH 1) monitoring electrical channel
LED red/yellow (CH 2, CH 3) monitoring optical channels
Ambient conditions
Operating temperature 0 ºC to +60 ºC
Storage/transport temperature -40 ºC to +70 ºC
Relative humidity <95% (non-condensing)
Mechanical construction
Dimensions (W x H x D) 40 x 140 x 77.5 mm
Mounting DIN rail or mounting plate
Weight 500 g
Protection class IP 40
Housing material die-cast zink
EMC interference immunity
EN 61000-4-2 electrostatic discharge (ESD) contact discharge: 6 kV, air discharge: 8 kV
EN 61000-4-3 electromagnetic field 10 V/m (80 - 1000 MHz)
EN 61000-4-4 fast transients (burst) power line 2 kV, data line: 1 kV
EN 61000-4-5 surge voltage power line 0.5 kV (line/line, line/earth), data line: 1 kV
EN 61000-4-6 conducted immunity 10 V (0.15 - 80 MHz)
EMC emitted immunity
EN 55022 EN 55022 limit class A
Approvals
Issued approvals FM Class 1, Div. 2; ATEX Zone 2; C-Tick
Scope of delivery and accessories
Scope of delivery device, start-up instructions
Accessories to order separately manual, order no. 039 629-001