OZD Profi 12M
G12-1300 EEC |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Product description |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Description |
 |
 |
 |
interface converter
electrical/optical for PROFIBUS-field bus networks; repeater
function; for quartz glass FO; long-haul version; approval for Ex-zone
2 (Class 1, Div. 2);
extended temperature and humidity range |
 |
 |
 |
 |
 |
 |
 |
Port type and quantity |
 |
 |
 |
2 x optical: 4 sockets
BFOC 2.5 (STR)
1 x electrical: Sub-D 9-pin, female, pin assignment according to EN
50170 part 1 |
 |
 |
 |
 |
 |
 |
 |
Type |
 |
 |
 |
OZD Profi 12M G12-1300
EEC |
 |
 |
 |
 |
 |
 |
 |
Order No. |
 |
 |
 |
943 256-321 |
 |
 |
 |
 |
 |
 |
 |
Electrical interface |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Signal type |
 |
 |
 |
PROFIBUS (DP-V0, DP-V1,
DP-V2 und FMS) |
 |
 |
 |
 |
 |
 |
 |
Bit rate |
 |
 |
 |
9.6; 19.2; 45.45;
93.75; 187.5; 500 kbit/s;
1.5; 3; 6; 12 Mbit/s (automatic setting) |
 |
 |
 |
 |
 |
 |
 |
Signal delay time (optional
input/output) |
 |
 |
 |
<= 6.5 bit times |
 |
 |
 |
 |
 |
 |
 |
Input/output signal |
 |
 |
 |
RS 485 level |
 |
 |
 |
 |
 |
 |
 |
Input voltage range |
 |
 |
 |
-7 V ... +12 V |
 |
 |
 |
 |
 |
 |
 |
Galvanic isolation |
 |
 |
 |
no |
 |
 |
 |
 |
 |
 |
 |
Optical interface |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Wavelength |
 |
 |
 |
1310 nm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in
single-mode fiber (SM) 9/125 |
 |
 |
 |
-19 dBm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in
multi-mode fiber (MM) 50/125 |
 |
 |
 |
-17 dBm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in
multi-mode fiber (MM) 62.5/125 |
 |
 |
 |
-17 dBm |
 |
 |
 |
 |
 |
 |
 |
Optical input power |
 |
 |
 |
min. -29 dBm, max.
-3 dBm |
 |
 |
 |
 |
 |
 |
 |
Cascadibility |
 |
 |
 |
not limited |
 |
 |
 |
 |
 |
 |
 |
More Interfaces |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Power supply |
 |
 |
 |
5-pin terminal block,
screw mounting |
 |
 |
 |
 |
 |
 |
 |
Signaling contact |
 |
 |
 |
5-pin terminal block,
screw mounting |
 |
 |
 |
 |
 |
 |
 |
Measuring outputs "Optical
input power" |
 |
 |
 |
2 mm sockets |
 |
 |
 |
 |
 |
 |
 |
Network size
- length of cable |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Single mode fiber (SM) 9/125
µm |
 |
 |
 |
15000 m
10 dB link budget at 1310 nm; A = 0.5 dB/km, 2 dB reserve |
 |
 |
 |
 |
 |
 |
 |
Multimode fiber (MM) 50/125
µm |
 |
 |
 |
10000 m
12 dB link budget at 1310 nm; A = 1 dB/km, 2 dB reserve |
 |
 |
 |
 |
 |
 |
 |
Multimode fiber (MM) 62.5/125
µm |
 |
 |
 |
10000 m
12 dB link budget at 1310 nm; A = 1 dB/km, 2 dB reserve |
 |
 |
 |
 |
 |
 |
 |
Power requirements |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Operating voltage |
 |
 |
 |
18 ... 32 VDC, typ.
24 VDC |
 |
 |
 |
 |
 |
 |
 |
Galvanic isolation |
 |
 |
 |
yes |
 |
 |
 |
 |
 |
 |
 |
Current consumption |
 |
 |
 |
max. 200 mA |
 |
 |
 |
 |
 |
 |
 |
Power consumption |
 |
 |
 |
4.8 W |
 |
 |
 |
 |
 |
 |
 |
Output voltage/output current
(pin6) |
 |
 |
 |
5 VDC +5%, -10%, short
circuit-proof/90 mA |
 |
 |
 |
 |
 |
 |
 |
Redundancy |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Redundancy functions |
 |
 |
 |
HIPER-Ring (ring structure),
redundant 24 V infeed |
 |
 |
 |
 |
 |
 |
 |
Displays |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
LED red/green (system) |
 |
 |
 |
monitoring operating
voltage and bit rate |
 |
 |
 |
 |
 |
 |
 |
LED red/yellow (CH 1) |
 |
 |
 |
monitoring electrical
channel |
 |
 |
 |
 |
 |
 |
 |
LED red/yellow (CH 2, CH 3) |
 |
 |
 |
monitoring optical
channels |
 |
 |
 |
 |
 |
 |
 |
Ambient conditions |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Operating temperature |
 |
 |
 |
-20 ºC to +60 ºC |
 |
 |
 |
 |
 |
 |
 |
Storage/transport temperature |
 |
 |
 |
-40 ºC to +70 ºC |
 |
 |
 |
 |
 |
 |
 |
Relative humidity |
 |
 |
 |
100% (condensing) |
 |
 |
 |
 |
 |
 |
 |
Mechanical construction |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Dimensions (W x H x D) |
 |
 |
 |
40 x 140 x 77.5 mm |
 |
 |
 |
 |
 |
 |
 |
Mounting |
 |
 |
 |
DIN rail or mounting
plate |
 |
 |
 |
 |
 |
 |
 |
Weight |
 |
 |
 |
500 g |
 |
 |
 |
 |
 |
 |
 |
Protection class |
 |
 |
 |
IP 40 |
 |
 |
 |
 |
 |
 |
 |
Housing material |
 |
 |
 |
die-cast zink |
 |
 |
 |
 |
 |
 |
 |
EMC interference
immunity |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-2 electrostatic
discharge (ESD) |
 |
 |
 |
contact discharge:
6 kV, air discharge: 8 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-3 electromagnetic
field |
 |
 |
 |
10 V/m (80 - 1000
MHz) |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-4 fast transients
(burst) |
 |
 |
 |
power line 2 kV, data
line: 1 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-5 surge voltage |
 |
 |
 |
power line 0.5 kV
(line/line, line/earth), data line: 1 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-6 conducted immunity |
 |
 |
 |
10 V (0.15 - 80 MHz) |
 |
 |
 |
 |
 |
 |
 |
EMC emitted
immunity |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
EN 55022 |
 |
 |
 |
EN 55022 limit class
A |
 |
 |
 |
 |
 |
 |
 |
Approvals |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Issued approvals |
 |
 |
 |
FM Class 1, Div. 2;
ATEX Zone 2; C-Tick |
 |
 |
 |
 |
 |
 |
 |
Scope of delivery
and accessories |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Scope of delivery |
 |
 |
 |
device, start-up instructions |
 |
 |
 |
 |
 |
 |
 |
Accessories to order separately |
 |
 |
 |
manual, order no.
039 629-001 |
 |
 |
 |
 |