OZD Profi 12M G12 EEC |
|
|
|
|
|
|
|
|
|
|
Product description |
|
|
|
|
|
|
|
|
|
|
|
Description |
|
|
|
interface converter electrical/optical for PROFIBUS-field bus networks; repeater function; for quartz glass FO; approval for Ex-zone 2; (Class 1, Div. 2); extended temperature and humidity range |
|
|
|
|
|
|
|
Port type and quantity |
|
|
|
2 x optical: 4 sockets BFOC 2.5 (STR) 1 x electrical: Sub-D 9-pin, female, pin assignment according to EN 50170 part 1 |
|
|
|
|
|
|
|
Type |
|
|
|
OZD Profi 12M G12 EEC |
|
|
|
|
|
|
|
Order No. |
|
|
|
943 730-321 |
|
|
|
|
|
|
|
Electrical interface |
|
|
|
|
|
|
|
|
|
|
|
Signal type |
|
|
|
PROFIBUS (DP-V0, DP-V1, DP-V2 und FMS) |
|
|
|
|
|
|
|
Bit rate |
|
|
|
9.6; 19.2; 45.45; 93.75; 187.5; 500 kbit/s; 1.5; 3; 6; 12 Mbit/s (automatic setting) |
|
|
|
|
|
|
|
Signal delay time (optional input/output) |
|
|
|
<= 6.5 bit times |
|
|
|
|
|
|
|
Input/output signal |
|
|
|
RS 485 level |
|
|
|
|
|
|
|
Input voltage range |
|
|
|
-7 V ... +12 V |
|
|
|
|
|
|
|
Galvanic isolation |
|
|
|
no |
|
|
|
|
|
|
|
Optical interface |
|
|
|
|
|
|
|
|
|
|
|
Wavelength |
|
|
|
860 nm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) 50/125 |
|
|
|
-15 dBm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) 62.5/125 |
|
|
|
-13 dBm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) HCS 200/230 |
|
|
|
-10 dBm (transmitting power default) |
|
|
|
|
|
|
|
Optical input power |
|
|
|
min. -28 dBm, max. -3 dBm |
|
|
|
|
|
|
|
Cascadibility |
|
|
|
not limited |
|
|
|
|
|
|
|
More Interfaces |
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
5-pin terminal block, screw mounting |
|
|
|
|
|
|
|
Signaling contact |
|
|
|
5-pin terminal block, screw mounting |
|
|
|
|
|
|
|
Measuring outputs "Optical input power" |
|
|
|
2 mm sockets |
|
|
|
|
|
|
|
Network size - length of cable |
|
|
|
|
|
|
|
|
|
|
|
Multimode fiber (MM) 50/125 µm |
|
|
|
3000 m 13 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
Multimode fiber (MM) 62.5/125 µm |
|
|
|
3000 m 15 dB link budget at 860 nm; A = 3.5 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
Multimode fiber HCS (MM) 200/230 µm |
|
|
|
1000 m 18 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
Power requirements |
|
|
|
|
|
|
|
|
|
|
|
Operating voltage |
|
|
|
18 ... 32 VDC, typ. 24 VDC |
|
|
|
|
|
|
|
Galvanic isolation |
|
|
|
yes |
|
|
|
|
|
|
|
Current consumption |
|
|
|
max. 200 mA |
|
|
|
|
|
|
|
Power consumption |
|
|
|
4.8 W |
|
|
|
|
|
|
|
Output voltage/output current (pin6) |
|
|
|
5 VDC +5%, -10%, short circuit-proof/90 mA |
|
|
|
|
|
|
|
Redundancy |
|
|
|
|
|
|
|
|
|
|
|
Redundancy functions |
|
|
|
HIPER-Ring (ring structure), redundant 24 V infeed |
|
|
|
|
|
|
|
Displays |
|
|
|
|
|
|
|
|
|
|
|
LED red/green (system) |
|
|
|
monitoring operating voltage and bit rate |
|
|
|
|
|
|
|
LED red/yellow (CH 1) |
|
|
|
monitoring electrical channel |
|
|
|
|
|
|
|
LED red/yellow (CH 2, CH 3) |
|
|
|
monitoring optical channels |
|
|
|
|
|
|
|
Ambient conditions |
|
|
|
|
|
|
|
|
|
|
|
Operating temperature |
|
|
|
-20 ºC to +60 ºC |
|
|
|
|
|
|
|
Storage/transport temperature |
|
|
|
-40 ºC to +70 ºC |
|
|
|
|
|
|
|
Relative humidity |
|
|
|
100% (condensing) |
|
|
|
|
|
|
|
Mechanical construction |
|
|
|
|
|
|
|
|
|
|
|
Dimensions (W x H x D) |
|
|
|
40 x 140 x 77.5 mm |
|
|
|
|
|
|
|
Mounting |
|
|
|
DIN rail or mounting plate |
|
|
|
|
|
|
|
Weight |
|
|
|
500 g |
|
|
|
|
|
|
|
Protection class |
|
|
|
IP 40 |
|
|
|
|
|
|
|
Housing material |
|
|
|
die-cast zink |
|
|
|
|
|
|
|
EMC interference immunity |
|
|
|
|
|
|
|
|
|
|
|
EN 61000-4-2 electrostatic discharge (ESD) |
|
|
|
contact discharge: 6 kV, air discharge: 8 kV |
|
|
|
|
|
|
|
EN 61000-4-3 electromagnetic field |
|
|
|
10 V/m (80 - 1000 MHz) |
|
|
|
|
|
|
|
EN 61000-4-4 fast transients (burst) |
|
|
|
power line 2 kV, data line: 1 kV |
|
|
|
|
|
|
|
EN 61000-4-5 surge voltage |
|
|
|
power line 0.5 kV (line/line, line/earth), data line: 1 kV |
|
|
|
|
|
|
|
EN 61000-4-6 conducted immunity |
|
|
|
10 V (0.15 - 80 MHz) |
|
|
|
|
|
|
|
EMC emitted immunity |
|
|
|
|
|
|
|
|
|
|
|
EN 55022 |
|
|
|
EN 55022 limit class A |
|
|
|
|
|
|
|
Approvals |
|
|
|
|
|
|
|
|
|
|
|
Issued approvals |
|
|
|
FM Class 1, Div. 2; ATEX Zone 2; C-Tick |
|
|
|
|
|
|
|
Scope of delivery and accessories |
|
|
|
|
|
|
|
|
|
|
|
Scope of delivery |
|
|
|
device, start-up instructions |
|
|
|
|
|
|
|
Accessories to order separately |
|
|
|
manual, order no. 039 629-001 |
|
|
|
|