|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OZD 485 G12 |
|
|
|
|
|
|
|
|
|
|
Product description |
|
|
|
|
|
|
|
|
|
|
|
Description |
|
|
|
Interface converter electrical/optical for RS 485 field bus networks; repeater function; for quartz glass FO; electrical full duplex or semi-duplex mode |
|
|
|
|
|
|
|
Port type and quantity |
|
|
|
2 x optical: BFOC 2.5 (STR) socket 1 x electrical: 12-pin terminal block |
|
|
|
|
|
|
|
Type |
|
|
|
OZD 485 G12 |
|
|
|
|
|
|
|
Order No. |
|
|
|
943 776-321 |
|
|
|
|
|
|
|
Electrical interface |
|
|
|
|
|
|
|
|
|
|
|
Signal type |
|
|
|
RS 485 (Modbus, ...) |
|
|
|
|
|
|
|
Input resistance |
|
|
|
10 kOhm |
|
|
|
|
|
|
|
Input voltage range |
|
|
|
-7 V ... +12 V |
|
|
|
|
|
|
|
Jitter |
|
|
|
typ. 10 nspp |
|
|
|
|
|
|
|
Distortion of bit duration |
|
|
|
typ. 1 nspp |
|
|
|
|
|
|
|
Bit rate |
|
|
|
0 to 1,5 Mbit/s NRZ |
|
|
|
|
|
|
|
Optical interface |
|
|
|
|
|
|
|
|
|
|
|
Wavelength |
|
|
|
860 nm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) 50/125 |
|
|
|
-20 dBm |
|
|
|
|
|
|
|
Launchable optical power in multi-mode fiber (MM) 62.5/125 |
|
|
|
-16 dBm |
|
|
|
|
|
|
|
Optical input power |
|
|
|
-30 dBm |
|
|
|
|
|
|
|
More Interfaces |
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
5-pin terminal block |
|
|
|
|
|
|
|
Signaling contact |
|
|
|
5-pin terminal block |
|
|
|
|
|
|
|
Voltage output |
|
|
|
3-pin terminal block |
|
|
|
|
|
|
|
Network size - length of cable |
|
|
|
|
|
|
|
|
|
|
|
Multimode fiber (MM) 50/125 µm |
|
|
|
2300 m 10 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
Multimode fiber (MM) 62.5/125 µm |
|
|
|
3100 m 14 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve |
|
|
|
|
|
|
|
System delay time |
|
|
|
<1,33 us |
|
|
|
|
|
|
|
Power requirements |
|
|
|
|
|
|
|
|
|
|
|
Operating voltage |
|
|
|
18 ... 32 VDC (typ. 24 VDC) |
|
|
|
|
|
|
|
Current consumption |
|
|
|
190 mA at 18 VDC, 110 mA at 32 VDC |
|
|
|
|
|
|
|
Power consumption |
|
|
|
3.4 W at 18 VDC, 3.5 W at 32 VDC |
|
|
|
|
|
|
|
Redundancy |
|
|
|
|
|
|
|
|
|
|
|
Redundancy functions |
|
|
|
redundant ring, redundant power supply |
|
|
|
|
|
|
|
Displays |
|
|
|
|
|
|
|
|
|
|
|
LEDs |
|
|
|
system (operating status, signaling contact); supply voltage; redundancy mode; input signal/input power/receiving data |
|
|
|
|
|
|
|
Ambient conditions |
|
|
|
|
|
|
|
|
|
|
|
Operating temperature |
|
|
|
-25 ºC to +60 ºC |
|
|
|
|
|
|
|
Storage/transport temperature |
|
|
|
-25 ºC to +70 ºC |
|
|
|
|
|
|
|
Relative humidity |
|
|
|
<95% (non-condensing) |
|
|
|
|
|
|
|
Mechanical construction |
|
|
|
|
|
|
|
|
|
|
|
Dimensions (W x H x D) |
|
|
|
40 x 140 x 90 mm |
|
|
|
|
|
|
|
Mounting |
|
|
|
DIN rail or mounting plate |
|
|
|
|
|
|
|
Weight |
|
|
|
650 g |
|
|
|
|
|
|
|
Protection class |
|
|
|
IP 30 |
|
|
|
|
|
|
|
Housing material |
|
|
|
die-cast zink |
|
|
|
|
|
|
|
EMC interference immunity |
|
|
|
|
|
|
|
|
|
|
|
EN 61000-4-2 electrostatic discharge (ESD) |
|
|
|
contact discharge: 4 kV, air discharge: 8 kV |
|
|
|
|
|
|
|
EN 61000-4-3 electromagnetic field |
|
|
|
10 V/m (80 - 1000 MHz) |
|
|
|
|
|
|
|
EN 61000-4-4 fast transients (burst) |
|
|
|
power line 2 kV, data line: 1 kV |
|
|
|
|
|
|
|
EN 61000-4-5 surge voltage |
|
|
|
power line 1 kV2 kV (line/line, line/earth), data line: 1 kV |
|
|
|
|
|
|
|
EN 61000-4-6 conducted immunity |
|
|
|
10 V (0.15 - 80 MHz) |
|
|
|
|
|
|
|
EMC emitted immunity |
|
|
|
|
|
|
|
|
|
|
|
EN 55022 |
|
|
|
EN 55022 limit class A |
|
|
|
|
|
|
|
Approvals |
|
|
|
|
|
|
|
|
|
|
|
Issued approvals |
|
|
|
cUL508, cUL1604 Hazardous Locations Class1 Div 2 Groups, ATEX 100a Zone 2 3G |
|
|
|
|
|
|
|
Scope of delivery and accessories |
|
|
|
|
|
|
|
|
|
|
|
Scope of delivery |
|
|
|
device, start-up instructions |
|
|
|
|
|
|
|
Accessories to order separately |
|
|
|
manual, order no. 039 516-001 |
|
|
|
|