OZD 485 G12 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Product description |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Description |
 |
 |
 |
Interface converter electrical/optical for RS 485 field bus networks; repeater function; for quartz glass FO; electrical full duplex or semi-duplex mode |
 |
 |
 |
 |
 |
 |
 |
Port type and quantity |
 |
 |
 |
2 x optical: BFOC 2.5 (STR) socket 1 x electrical: 12-pin terminal block |
 |
 |
 |
 |
 |
 |
 |
Type |
 |
 |
 |
OZD 485 G12 |
 |
 |
 |
 |
 |
 |
 |
Order No. |
 |
 |
 |
943 776-321 |
 |
 |
 |
 |
 |
 |
 |
Electrical interface |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Signal type |
 |
 |
 |
RS 485 (Modbus, ...) |
 |
 |
 |
 |
 |
 |
 |
Input resistance |
 |
 |
 |
10 kOhm |
 |
 |
 |
 |
 |
 |
 |
Input voltage range |
 |
 |
 |
-7 V ... +12 V |
 |
 |
 |
 |
 |
 |
 |
Jitter |
 |
 |
 |
typ. 10 nspp |
 |
 |
 |
 |
 |
 |
 |
Distortion of bit duration |
 |
 |
 |
typ. 1 nspp |
 |
 |
 |
 |
 |
 |
 |
Bit rate |
 |
 |
 |
0 to 1,5 Mbit/s NRZ |
 |
 |
 |
 |
 |
 |
 |
Optical interface |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Wavelength |
 |
 |
 |
860 nm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in multi-mode fiber (MM) 50/125 |
 |
 |
 |
-20 dBm |
 |
 |
 |
 |
 |
 |
 |
Launchable optical power in multi-mode fiber (MM) 62.5/125 |
 |
 |
 |
-16 dBm |
 |
 |
 |
 |
 |
 |
 |
Optical input power |
 |
 |
 |
-30 dBm |
 |
 |
 |
 |
 |
 |
 |
More Interfaces |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Power supply |
 |
 |
 |
5-pin terminal block |
 |
 |
 |
 |
 |
 |
 |
Signaling contact |
 |
 |
 |
5-pin terminal block |
 |
 |
 |
 |
 |
 |
 |
Voltage output |
 |
 |
 |
3-pin terminal block |
 |
 |
 |
 |
 |
 |
 |
Network size - length of cable |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Multimode fiber (MM) 50/125 µm |
 |
 |
 |
2300 m 10 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve |
 |
 |
 |
 |
 |
 |
 |
Multimode fiber (MM) 62.5/125 µm |
 |
 |
 |
3100 m 14 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve |
 |
 |
 |
 |
 |
 |
 |
System delay time |
 |
 |
 |
<1,33 us |
 |
 |
 |
 |
 |
 |
 |
Power requirements |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Operating voltage |
 |
 |
 |
18 ... 32 VDC (typ. 24 VDC) |
 |
 |
 |
 |
 |
 |
 |
Current consumption |
 |
 |
 |
190 mA at 18 VDC, 110 mA at 32 VDC |
 |
 |
 |
 |
 |
 |
 |
Power consumption |
 |
 |
 |
3.4 W at 18 VDC, 3.5 W at 32 VDC |
 |
 |
 |
 |
 |
 |
 |
Redundancy |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Redundancy functions |
 |
 |
 |
redundant ring, redundant power supply |
 |
 |
 |
 |
 |
 |
 |
Displays |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
LEDs |
 |
 |
 |
system (operating status, signaling contact); supply voltage; redundancy mode; input signal/input power/receiving data |
 |
 |
 |
 |
 |
 |
 |
Ambient conditions |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Operating temperature |
 |
 |
 |
-25 ºC to +60 ºC |
 |
 |
 |
 |
 |
 |
 |
Storage/transport temperature |
 |
 |
 |
-25 ºC to +70 ºC |
 |
 |
 |
 |
 |
 |
 |
Relative humidity |
 |
 |
 |
<95% (non-condensing) |
 |
 |
 |
 |
 |
 |
 |
Mechanical construction |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Dimensions (W x H x D) |
 |
 |
 |
40 x 140 x 90 mm |
 |
 |
 |
 |
 |
 |
 |
Mounting |
 |
 |
 |
DIN rail or mounting plate |
 |
 |
 |
 |
 |
 |
 |
Weight |
 |
 |
 |
650 g |
 |
 |
 |
 |
 |
 |
 |
Protection class |
 |
 |
 |
IP 30 |
 |
 |
 |
 |
 |
 |
 |
Housing material |
 |
 |
 |
die-cast zink |
 |
 |
 |
 |
 |
 |
 |
EMC interference immunity |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-2 electrostatic discharge (ESD) |
 |
 |
 |
contact discharge: 4 kV, air discharge: 8 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-3 electromagnetic field |
 |
 |
 |
10 V/m (80 - 1000 MHz) |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-4 fast transients (burst) |
 |
 |
 |
power line 2 kV, data line: 1 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-5 surge voltage |
 |
 |
 |
power line 1 kV2 kV (line/line, line/earth), data line: 1 kV |
 |
 |
 |
 |
 |
 |
 |
EN 61000-4-6 conducted immunity |
 |
 |
 |
10 V (0.15 - 80 MHz) |
 |
 |
 |
 |
 |
 |
 |
EMC emitted immunity |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
EN 55022 |
 |
 |
 |
EN 55022 limit class A |
 |
 |
 |
 |
 |
 |
 |
Approvals |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Issued approvals |
 |
 |
 |
cUL508, cUL1604 Hazardous Locations Class1 Div 2 Groups, ATEX 100a Zone 2 3G |
 |
 |
 |
 |
 |
 |
 |
Scope of delivery and accessories |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Scope of delivery |
 |
 |
 |
device, start-up instructions |
 |
 |
 |
 |
 |
 |
 |
Accessories to order separately |
 |
 |
 |
manual, order no. 039 516-001 |
 |
 |
 |
 |