Industrial Networking
FiberINTERFACES
Digital
Field Bus
Universal RS 485 Fiberoptic Repeaters
PROFIBUS Fiberoptic Repeaters
Genius Bus Fiberoptic Repeaters
FIP Bus Fiberoptic Repeaters
Modbus Plus Fiberoptic Repeaters
Video
Hybrids modules and OptoQuick components
Accessories
Industrial Ethernet
         
OZD 485 G12 BAS
Product description
Description Interface converter electrical/optical for RS 485 field bus networks; repeater function; for quartz glass FO; electrical semi-duplex mode
Port type and quantity 2 x optical: BFOC 2.5 (STR) socket
1 x electrical: 6-pin terminal block
Type OZD 485 G12 BAS
Order No. 943 893-321
Electrical interface
Signal type RS 485
Input resistance 10 kOhm
Input voltage range -7 V ... +12 V
Jitter typ. 10 nspp
Distortion of bit duration typ. 1 nspp
Bit rate 0 to 1.5 Mbit/s NRZ
Optical interface
Wavelength 860 nm
Launchable optical power in multi-mode fiber (MM) 50/125 -20 dBm
Launchable optical power in multi-mode fiber (MM) 62.5/125 -16 dBm
Optical input power -30 dBm
More Interfaces
Power supply 5-pin terminal block
Network size - length of cable
Multimode fiber (MM) 50/125 µm 2300 m
10 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve
Multimode fiber (MM) 62.5/125 µm 3100 m
14 dB link budget at 860 nm; A = 3.5 dB/km, 3 dB reserve
System delay time <1,56 us
Power requirements
Operating voltage 18 ... 32 VDC (typ. 24 VDC)
Current consumption 80 mA at 24 VDC, 65 mA at 32 VDC
Power consumption <2,1 W
Displays
LEDs system (operating status) receiving data
Ambient conditions
Operating temperature 0 ºC to +60 ºC
Storage/transport temperature -25 ºC to +80 ºC
Relative humidity <95% (non-condensing)
Mechanical construction
Dimensions (W x H x D) 35x156x119
Mounting DIN rail
Weight 180 g
Protection class IP 20
Housing material plastics
EMC interference immunity
EN 61000-4-2 electrostatic discharge (ESD) contact discharge: 4 kV, air discharge: 8 kV
EN 61000-4-3 electromagnetic field 10 V/m (80 - 1000 MHz and 1400 - 2000 MHz)
EN 61000-4-4 fast transients (burst) power line 2 kV, data line: 1 kV
EN 61000-4-5 surge voltage power line 1 kV (line/line, line/earth), data line: 1 kV
EN 61000-4-6 conducted immunity 10 V (0.15 - 80 MHz)
EMC emitted immunity
EN 55022 EN 55022 limit class A
Scope of delivery and accessories
Scope of delivery device, start-up instructions
Accessories to order separately manual, order no. 039 516-001